Transformers are electromagnetic devices that transfer electrical      
energy from one circuit to another by mutual induction. Mutual       
induction is the coupling of inductances by their mutual       
magnetic fields. In a single-phase transformer there are two       
coils, a primary and a secondary coil. The following circuit       
illustrates mutual induction. The AC generator provides electrical       
power to the primary coil. The magnetic field produced by       
the primary induces a voltage into the secondary coil, which       
supplies power to a load
Transformers are used to step a voltage up to a higher level,      
or down to a lower level. Transformers are used extensively       
in power distribution systems, allowing power companies       
to transfer electrical energy many miles. Power generators       
typically generate high voltages. This voltage varies, depending       
on the generator, but a typical voltage might be 15 KV. The       
voltage is stepped up through a transformer to higher levels       
for transmission to substations. Typical voltages range from       
115 KV to 765 KV. The electrical power is received at substation       
transformers many miles away where it is stepped down.       
Typical voltage might be 34 KV or 69 KV. From here, electrical       
power is fed to a distribution substation. It can also be fed       
directly to factory locations. If the power is fed to a factory,       
transformers at the factory site reduce the voltage to usable       
levels. The power fed to a distribution substation is reduced by       
transformers at the substation for factory and home use.
Coefficient of Coupling
Mutual inductance between two coils depends on their flux      
linkage. Maximum coupling occurs when all the lines of flux       
from the primary coil cut through the secondary winding.       
The amount of coupling which takes place is referred to as       
coefficient of coupling. To maximize coefficient of coupling, both       
coils are often wound on an iron core which is used to provide       
a path for the lines of flux. The following discussion of step-up       
and step-down transformers applies to transfers with an iron core
There is a direct relationship between voltage, impedance,      
current, and the number of coil turns in a transformer. This       
relationship can be used to find either primary or secondary       
voltage, current, and the number of turns in each coil. It is the       
number of turns which determine if a transformer is a step up       
or step down transformer. The following “rules-of-thumb” apply       
to transformers:       
• If the primary coil has fewer turns than the secondary coil,       
it is a step-up transformer.       
• If the primary coil has more turns than the secondary coil,       
it is a step-down transformer.       
When the number of turns on the primary and secondary coils of       
a transformer are equal, input voltage, impedance, and current       
are equal to output voltage, impedance, and current.
Step-Up Transformer
A step-up transformer is used when it is desirable to step      
voltage up in value. The following circuit illustrates a stepup       
transformer. The primary coil has fewer turns than the       
secondary coil. The number of turns in a transformer is given as       
a ratio. When the primary has fewer turns than the secondary,       
voltage and impedance are stepped up. In the circuit illustrated,       
voltage is stepped up from 120 VAC to 240 VAC. Because       
impedance is also stepped up, current is stepped down from 10       
amps to 5 amps
Step-Down Transformer
A step-down transformer is used when it is desirable to      
step voltage down in value. The following circuit illustrates a       
step-down transformer. The primary coil has more turns than       
the secondary coil. The step-down ratio is 2:1. voltage and       
impedance are stepped down, current is stepped up
Single-Phase Transformer
120 or 240 VAC single-phase transformers are used to supply      
lighting, receptacle, and small appliance loads. A transformer       
with a 240 VAC secondary can be used to supply 240 VAC to       
larger appliances such as stoves, air conditioners and heaters.       
A 240 VAC secondary can be tapped in the center to provide       
two sources of 120 VAC power
Formulas for Calculating the Number of Primary and Secondary Turns of a Transformer
There  are a number of useful formulas for calculating, voltage,      
current, and the number of turns between the primary and       
a secondary of a transformer. These formulas can be used with       
either step-up or step-down transformers. The following legend       
applies to the transformer formulas
ES = secondary voltage      
EP = primary voltage       
IS = secondary current       
IP = primary current       
NS = turns in the secondary coil       
NP = turns in the primary coil
Using the values for the step-down transformer in the example      
of the previous page, the secondary voltage can be verified
Transformer Ratings
Transformers are rated in kVA (kilovolt-amps). This rating is      
used rather than watts because loads are not purely resistive.       
Only resistive loads are measured in watts. The kVA rating       
determines the current a transformer can deliver to its load       
without overheating. Given volts and amps, kVA can be       
calculated. Given kVA and volts, amps can be calculated
Using the illustrated step-down transformer, the kVA rating can      
be calculated. The kVA rating of a transformer is the same for       
both the primary and the secondary
 
 
No comments:
Post a Comment